All Compact-Power™ battery deliveries carry a
detailed installation and operating guide.
The following points are reminded.
Before connecting the battery to the charger or busbar or any electrical circuit check the polarity of each unit in the string and of the whole string.
Place the Kelvin-Arrhenius-Monitors™. Pay attention to live electrical parts.
Start-up the electrical equipment according to the manufacturers specifications.
Check the voltage applied to the battery as soon as feasible and after 3-6 weeks of first operation.
Measure average room and battery temperature and adjust float voltage according to the operating instructions when the ambient temperature is expected to be permanently outside the +18 to +25 °C (+64 to+77 °F) range.
Keep the battery installation clean. Use only a damp cloth to clean cells and monoblocs. Never use solvents and chemicals. Watch for live electrical parts and do not clean with dry dusters so to avoid electrostatic discharges/sparks.
Do not smoke or entertain open flames in a battery room. Keep the access to the room or the interior of cabinets limited to qualified personnel. Post warning signs and keep aisle room sized for safe escape according to local laws and regulations.
![]() |
|
![]() |
|
![]() |