All exposed metal parts of a battery are live and so there is a danger of injury from electric shock and of accidental short circuits. Be carefull with non insulated tools, bracelets and rings. Touch the battery on the plastic surfaces only.



Compact-Power™ cells and monoblocs have very low internal resistance and can deliver large short circuit currents. These currents have been determined with the two current level pulse method according to the International Standard IEC 896-2,1996. Compact Power™ units can withstand their own short circuit current for 1 minute. Battery installations should be protected according the equipment power output and cross-section of the installed cables. The fuse or disconnecting equipment used must be capable to interrupt the current within 10s of the onset of the short circuit condition. Eventual magnetic forces arising from the short circuit current flow have to be considered. Fuse blowing or switch operation shall not causes a possible ignition of electrolysis gases.

The short-circuit current ISC of Compact-Power™ batteries is determined according to International Standard IEC 896-2. The following formula is used:

ISC=(U1) (I2) - (U2) (I1) / U1-U2
RI = U1 - U2 / I2 - I1

Type
Short-circuit ISC at 20 °C [A]
Internal resistance Ri at 20 °C charged 100 % [mOhm]
12 CP 25 1000 12.50
12 CP 26 1230 10.00
12 CP 39 1730 7.00
12 CP 50 1900 6.30
12 CP 52 2200 5.50
12 CP 65 2560 4.80
12 CP 100 3400 3.60
12 CP 150 5000 2.40
     
6 CP 60 1780 3.40
6 CP 80 2220 2.70
6 CP 100 2630 2.30
6 CP 115 3020 2.00
6 CP 135 3400 1.80
6 CP 155 3760 1.60
     
4 CP 185 5430 0.74
4 CP 205 5900 0.69
4 CP 225 6390 0.60
     
2 CP 180 4120 0.48
2 CP 240 5120 0.39
2 CP 300 6070 0.32
2 CP 345 6970 0.28
2 CP 405 7840 0.25
2 CP 465 8680 0.23
     
2 CP 450 7690 0.26
2 CP 550 9090 0.22
2 CP 650 10500 0.19
2 CP 800 13300 0.15
2 CP 900 15400 0.13
2 CP1000 18200 0.11
Sitemap
Glossary
Career
Career
Links
Download
Imprint
Disclaimer
Contact

Contact
Home
Installation / Ventilation Guideline
Operating position of Compact-Power™ cells and monoblocs
Battery strings
Ventilation of battery installations
Operating temperatures
Electromagnetic compatibility / AC power interaction with the battery
Fuse protection for the battery
Storage prior to installation
Installation and operation
Battery monitoring
   
   
   
Installation/Ventilation Guideline